Project: Singrauli STPS, Stage-II (2x500 MW)
Package: R&M of Fire Detection & Protection System Package
Salient Technical Features
1.0 The broad scope of works under R&M of Fire Detection and Protection System
Package include design, engineering, manufacture, testing at works, supply,
delivery and storage at site, erection, testing and commissioning of all fire
detection and protection system for areas/equipments, as detailed hereunder:
2.0 BRIEF DESCRIPTIOIN OF FIRE DETECTION AND PROTECTION SYSTEM:
The complete Fire Detection and Protection System shall be as per
guidelines/codes/standards/rules of TAC/NFPA/IS:3034/OISD, etc.
A comprehensive fire detection and protection system shall be provided by the
bidder in-line with above regulations broadly covering following areas with
equipment detailed below:
(a) Replacement of halon based fire protection system with inert gas fire
extinguishing system:
One (1) independent Inert gas system comprising of Inert gas cylinders
complete with gas & gas manifold, piping, various valves, pneumatic /
electric actuating devices, directional valves, nozzles & other accessories
for control equipment rooms of Unit-6 & 7, Programmer room of unit,
Common control room of unit-6 & 7, etc. located at 17.0 M EL. and CER,
UPS Room, Charger room, etc. located at 8.5 M EL. in main plant
building of Stage-II.
(b) Hydrant System:
(1) Internal hydrant system consisting of landing valves, hoses, branch pipe
& nozzle, hose box, etc. for staircase landings at various floors of existing
service building & administrative building.
(2) Internal hydrant system consisting of landing valves, hoses, branch pipe
& nozzle, hose box, etc. high rise conveyors (height greater than 30M) of
Stage-II.
(3) Water monitors with accessories and an isolation valve for coal stockyard
area.
(c) MVW Spray System:
(1) MVW spray system comprising of deluge valves, isolation valves,
strainers, nozzles, piping, etc. for cable galleries in TG building of Stage-II
and cable gallery in Switchyard building.
(2) MVW spray system comprising of deluge valves, isolation valves,
strainers, nozzles, QBDs, piping, etc. for the various coal conveyors,
bunker conveyors & TPs, crusher house of Stage-II.
(d) Foam Protection System:
(1) Automatic fixed foam protection system (Skid mounted foam bladder tank
assembly) for two (2) HPS Day Tanks.
(2) Automation of existing manual fixed foam protection system provided for
HFO tanks.
(e) Electrical and C&I works:
(1) Analogue addressable type fire alarm system consisting of multisensor
type detectors, LHSC detector, Infra-red type heat detectors, cabling,
junction boxes, instrumentation, fire alarm cum control panels, PC based