VINDHYACHAL STPP STAGE-IV (2 X 500 MW)
Augmentation/Modification Works of One Cooling Tower Package
Three (3) Nos Main cooling towers are already been provided by employer in VSTPP STAGE-IV
for condenser and unit auxiliary cooling water purposes. As the achieved cold water temperature
from cooling tower is higher than the design cold water temperature by around 5 Deg C, it is
proposed to modify/augment one number of existing cooling tower to achieve the design cold water
temperature.
The scope includes Design, Engineering, Manufacture, Supply, Construction, Erection, Testing &
Commissioning works for Modification/ Augmentation of one existing Induced draft Cooling
Towers and associated equipment’s for Vindhyachal Super Thermal Power Project-stage-IV (2 X
500 MW).
The Technical features of the Existing Cooling Towers are as follows:-
a) Type of existing cooling tower Induced Draft RCC cooling Tower,
Single Inlet Type
b) Number of existing Cooling Towers 3 (Three) numbers
c) Number of total cells per Cooling Tower 18 (Eighteen) numbers (16W+2S)
d) Design flow for each Cooling tower 40,000 Cu.M/hr
e) Range of Cooling 10.5 deg. C.
f) Design Cold Water temperature 32.5 deg C.
g) Design ambient wet bulb temperature 27.4 deg C.