Page 1 of 2
SALIENT TECHNICAL FEATURES
SALIENT TECHNICAL FEATURES
“Salient Technical Features of the equipment / systems / services covered in IFB No.
40087561 are mentioned below. These Salient Technical features are mentioned only to
facilitate the prospective bidders to prima-facie understand the requirements under the
tender and the bidder shall not in any way limit or alter the scope of work and technical
features/specification of equipment/system/services covered in the Bidding Documents.
Detailed provisions in regard of scope of work and technical features/specification of
equipment/systems /services, contained in the Bidding Documents shall be final and
binding”.
A. Brief Scope of Work:
The scope of Mobile Dry Sorbent Injection (DSI) System Package for Tanda Thermal
Power Station Stage-I, Unit 1 & 2 (2 x110 MW) shall cover design, engineering,
manufacture, shop fabrication, preassembly, shop testing/type testing at manufacturer’s
works, packing, transportation, unloading, handling and conservation of equipment at site,
complete services of construction including erection, supervision, pre-commissioning,
commissioning and performance testing of equipments under bidder’s scope of work of Mobile
Dry Sorbent Injection (DSI) System and its associated auxiliaries including all associated
Electrical, Control & Instrumentation works. Dry Sorbent Injection System shall use Sodium
Bicarbonate (SBC) as reagent and shall have but not limited to the following:
One no. of mobile Sodium Bicarbonate (SBC) Storage Silos complete with Truck
Unloading System to Storage Silos;
Sodium Bicarbonate Feeding system for Silo;
1 no. of SBC Mill of minimum 3000 kg/hr capacity for grinding sodium bicarbonate;
Injection system for feeding SBC at APH inlet & APH outlet in both the 110 MW units
(Unit 1 & 2);
Instrument air compressor;
Container for housing the DSI system;
Complete Electrical System including all motors, LT Switchgears, Transformer, Electrical
Actuators, LT power & control cables, cabling, lighting etc.
Complete C&I systems including SO
2
analyser.
First fill and one year topping requirement of consumables/oils/lubricants, supply of
special maintenance tools and tackles, commissioning spares, mandatory spares etc.
Supply & storage of 800 MT of semi-milled Sodium bicarbonate & 80 MT of hydrated lime;
Page 2 of 2
Operation and Maintenance of mobile DSI system including supply of spares &
consumables for six months;
Detailed scope of work has been specified in the bidding documents.
B. Other Technical Features:
1.00.00 Dry Sorbent Injection (DSI) System
1.01.00 System Description:
The DSI system shall be mobile system and shall be installed inside a
container. The DSI system for SO
2
control shall be based on Sodium Bicarbonate as
reagent. The mobile DSI system shall also have the capability to inject powdered
hydrated lime at to meet SO
2
emission. Sodium Bicarbonate shall be milled before
being injected at appropriate location at APH inlet & APH outlet for capturing of SO
2
in
the flue gas. ESPs are installed downstream of APH where the reactants shall be
collected along with ash.
1.02.00 Service Conditions
The Steam Generators are designed to burn pulverised coal. HFO/HPS/LSHS and
LDO shall be used during startup and at low loads for warm up and flame stablisation
of Steam Generator. The DSI system shall be designed to remove SO
2
(to meet the
stipulated SO
2
efficiency levels) from the flue gas generated in the Steam Generator
with pulverized coal firing. High efficiency Electrostatic Precipitators are installed