Page 1 / 1
Salient Technical Features
Transmission system package for Manglutan & Chidiyatapu
Solar Power Project(s) in South Andaman
Salient Technical Features of the equipment/ systems/ services covered in IFB No.
40087137 are mentioned below. These Salient Technical Features are mentioned
only to facilitate the prospective bidders to prima-facie understand the requirements
under the tender and shall not in any way limit or alter the scope of work and technical
features/specification of equipment/ systems/ services covered in the Bidding
Documents. Detailed provisions in regard of scope of work and technical
features/specification of equipment/ systems/ services, contained in the Bidding
Document shall be final and binding.”
The scope of work covers 33 kV transmission system alongwith 33/11 kV sub-station
for Manglutan & Chidiyatapu SPV project(s) in South Andaman which shall consist of
the following:
33/19 kV UG XLPE cable
AAAC equivalent to ACSR Panther/Dog conductor
33/11 kV sub-station including 1.6 MVA Transformer
33 &11 kV Outdoor equipment such as Isolators, Surge Arresters & Cable
terminations etc.
Insulated covered conductor/NBLS Towers
The system parameters for 33kV & 11 kV system shall be as under:
System Parameters 33 kV 11kV
Highest system voltage : 36 kVrms 12 kVrms
Lightning Impulse voltage : 170 kVp 75 kVp
Power frequency withstand
voltage for 1 min. (rms) : 70 kV (rms) 28 kV (rms)
Max. fault level (1 sec.) : 25 kA 12.5 kA
Minimum creepage distance : 1116 mm 372 mm