SALIENT TECHNICAL FEATURES

Complete Jocky Pump for Fire Water System with motor, coupling, sole plate and mandatory spares.

The offered pump to be used in place of existing pump of Make Fairbank Morse India Ltd. (Now Flowmore Ltd) Model 6M/7, No. of stages Seven (07)

Type: Vertical Turbine Pump

The technical specifications as required are given below.

-Type: Vertical Turbine Pump

-Duty: Continuous

-Rated Flow minimum 30 Cub M /Hr

-Rated Head: 90-105 MWC

-Pump Discharge Size: 100-150 NB

-MOC of shafts: SS 410

-MOC of Impellers: Bronze/ SS 410

-Pump Bearing Lubrication Self Water Lubricated

-Pump Bearing Type: Cutless Rubber/ Thordon.

-Type of Coupling: Flexible

-Liquid to be handled: Raw Water

-Specific Gravity 1.0

-Temperature Ambient: (5 - 50 Deg C)

-Depth of Sump from pump floor: 8.2 M

-Min Water Level of Sump: 2.7 M

-Max Water Level of Sump: 7.2 M

-Motor RPM: 3000

-Suitable Motor rating approx. 15 KW

-Motor Type: 3-phase, Squirrel Cage, 50 Hz

-Motor insulation class: F insulation class

-Motor duty: Continuous

-Motor protection class: IP 55

-Opening in the floor for installation of this pump (vertically) – 600 x 600 mm

Note: Pump must be compatible for installation in the existing opening as defined