SALIENT TECHNICAL FEATURES

SPECIFICATION FOR INLET AIR FILTERATION SYSTEM

Anta Gas Power Station

1.

2.

3.

4.

5.

6.

7.

High (Pulse start) set point

: 64 mm WC

Low (Pulse stop) set point

: 46 mm WC

Pulse duration

: 100 milisec.

Duration between consecutive pulses.

: 30 sec

Air flow/cartridge

: 737 CFM (at 270 C)

Comp air header pr.

: 7 bar

Comp. Air requirement for one

: 1.88 NM3/min

Gas Turbine

 

8.

Effective air flow rate through

: 0.35 m3/sec

 

Each cartridge

 

9.

Effective media velocity

: 0.015m/sec

10.

Approach air velocity

: 1.66 m/sec

11.

Max comp. Air temp.

: 770 C

12.

Effective surface area of filter media.

: 22.3 m2 (minimum)

13.

Numbers of Pleats

: 330 ± 2 nos.

14.

Length of cartridge

: 673 mm (approx.)

15.

Dia of cartridge

: 324

16.

Cartridge drawing

: Attached

17.

No. of filter cartridges/Gas Turbines

: 945 nos.

18.

No of Gas Turbine

: 3 nos.

19.

Filter media

: Impregnated filter media

 

 

Consisting of synthetic & cellulose

 

 

fiber of Holling Worth’s & Vouse Co.

 

 

of USA

20. Adhesive for bonding filter media to

: Thixotropic type

 

and plates

 

21. Original Manufacturers of the cartridge

: FARR, USA. Media

Paper-FA-2071