TANDA THERMAL POWER PROJECT-STAGE II, (2X660 MW)
Switchyard Package (CS-9562-563-2)
SALIENT TECHNICAL FEATURES
1. 400 kV GIS consisting of “One and Half Breaker Scheme” system with the following parameters:
a) Highest system voltage |
420 KV rms |
b) System Frequency |
50Hz |
c) Lightning Impulse Voltage |
|
-Phase to earth & between phases |
1425 KVp |
-Across isolating distance |
1425(+240) KV |
d) Switching Impulse Voltage |
|
-Phase to earth |
1050KVp |
-Across isolating distance |
900(+345) KV |
-Between phases |
1575KVp |
e) Power frequency withstand for 1(one) min (rms) |
|
-Phase to earth & between phases |
650KVrms |
-Across isolating distances |
815KVrms |
f) Max fault level (1 Sec.) |
50 kA |
g) PD level of GIS |
Less than 5 Pico Coulomb |
2. 400 kV AIS (Air insulated switchyard) parameters:
The system parameters shall be as under:
Highest system voltage : 420 kV rms
Lightning Impulse voltage : ±1425kVp
Switching impulse voltage : ±1050kVp
Power frequency withstand : 630kV (rms)
for 1 min. (rms) :
Max. fault level (1 sec.) : 50 kA
Minimum creepage distance : 10500 mm
3. 220 kV AIS (Air insulated switchyard) parameters:
The system parameters shall be as under:
Highest system voltage : 245 kV rms
Lightning Impulse voltage : ±1050kVp
Power frequency withstand : 460kV(rms)
for 1 min. (rms) :
Max. fault level (1 sec.) : 40 kA
Minimum creepage distance : 6125 mm