TANDA THERMAL POWER PROJECT-STAGE II, (2X660 MW)

Switchyard Package (CS-9562-563-2)

SALIENT TECHNICAL FEATURES

1. 400 kV GIS consisting of “One and Half Breaker Scheme” system with the following parameters:

a) Highest system voltage

420 KV rms

b) System Frequency

50Hz

c) Lightning Impulse Voltage

-Phase to earth & between phases

1425 KVp

-Across isolating distance

1425(+240) KV

d) Switching Impulse Voltage

-Phase to earth

1050KVp

-Across isolating distance

900(+345) KV

-Between phases

1575KVp

e) Power frequency withstand for

1(one) min (rms)

-Phase to earth & between phases

650KVrms

-Across isolating distances

815KVrms

f) Max fault level (1 Sec.)

50 kA

g) PD level of GIS

Less than 5 Pico Coulomb

2. 400 kV AIS (Air insulated switchyard) parameters:

The system parameters shall be as under:

Highest system voltage : 420 kV rms

Lightning Impulse voltage : ±1425kVp

Switching impulse voltage : ±1050kVp

Power frequency withstand : 630kV (rms)

for 1 min. (rms) :

Max. fault level (1 sec.) : 50 kA

Minimum creepage distance : 10500 mm

3. 220 kV AIS (Air insulated switchyard) parameters:

The system parameters shall be as under:

Highest system voltage : 245 kV rms

Lightning Impulse voltage : ±1050kVp

Power frequency withstand : 460kV(rms)

for 1 min. (rms) :

Max. fault level (1 sec.) : 40 kA

Minimum creepage distance : 6125 mm