NATURAL DRAFT COOLING TOWERS PACKAGE
The scope includes design, engineering, manufacture, inspection, testing at works, supply and installation at site, putting into initial operation and performance testing of Natural draft Cooling Towers, along with associated civil works for Tanda TPP
The brief scope and technical features of the Cooling towers Package are as follows:
Natural draft cooling towers:
a) |
Number of Induced draught RCC Cooling Towers |
2 (Two) numbers |
b) |
Design flow for each Cooling tower |
72,000 Cu.M/hr |
c) |
Range of Cooling |
10.5 deg. C. |
d) |
Design Cold Water temperature |
32.5 deg C. |
e) |
Design ambient wet bulb temperature |
27.4 deg C. |
f) |
Type of fill |
Splash type |
g)Required Cooling Water Channel from each Cooling tower up to the terminal point defined in tender documents.
h)Required Hot water pipes from the terminal point and associated branch isolation valves, cell isolation valves etc.
i)Complete Instrumentation as per bid document