‘AIR CONDITIONING AND VENTILATION SYSTEM’ PACKAGE
FOR
LARA SUPER THERMAL POWER PROJECT,
Salient Technical Features of the Equipments/ Systems/ Services covered in NIT/IFB No. 40026972 dated 18.09.2014 are mentioned below.
These Salient Technical Features are mentioned only to facilitate the prospective Bidders to
SALIENT TECHNICAL FEATURES
1.0BRIEF DESCRIPTION OF
It is proposed to provide Screw chilling machines to meet the air conditioning requirement of all the air conditioned areas of main plant.
1.1A/C Plant for Main Plant
1.1.1One Centralized Chilled Water Plant has been envisaged for:
(a)Control Rooms (CRs), Control Equipment Rooms (CERs).
(b)UPS, Battery Charger Room.
(c)SWAS Room.
1.1.2The A/C System would comprise of:
(i)3 x 185 TR capacity Screw Compressor type Chilling Machine.
(ii)Three (3) Nos. of Chilled Water Pumps.
(iii)One (1) No. of Condenser Water Pump.
(iv)One (1) No. of Cooling Tower.
(v)Eight (8) Nos. of Variable Frequency Driven (VFD) Air Handling Units (AHUs).
(vi)Interconnecting Piping, Duct Work, Insulation, Cabling, DCS based Control Panel, Instrumentation, etc.
Page 1 of 2
1.2A/C Plant for ESP Control Rooms
1.2.1The A/C System would comprise of:
(i)4 x 45 TR capacity
(ii)Four (4) Nos. of Variable Frequency Driven (VFD) Air Handling Units (AHUs).
(iii)Interconnecting Piping, Duct Work, Insulation, Cabling, DCS based Control Panel, Instrumentation, etc.
1.3A/C Plant for Water System Control Building
1.3.1The A/C System would comprise of:
(i)2 x 25 TR capacity
(ii)Two (2) Nos. of Variable Frequency Driven (VFD) Air Handling Units (AHUs).
(iii)Interconnecting Piping, Duct Work, Insulation, Cabling, DCS based Control Panel, Instrumentation, etc.
2.0BRIEF DESCRIPTION OF VENTILATION SYSTEM
2.1Main Power House
Twenty (20) Nos. of Modular type Air Washer Units (AWU) each of capacity 1,00,000 m3/hr and Two (2) Nos. of Air Washer Units
2.2ESP Control Room
To cater to the ventilation requirements of
2.3Supply Air Fans/Exhaust Air Fans/ Roof Extractor Fans with drive motors shall be provided for Pump Houses, MCC Rooms, Battery Rooms, Cable Galleries, Auxiliary Buildings, Toilets, etc.
2.4Ducts supplying air to Switchgear Rooms and Cable Spreader/ Vault Rooms in Main Power House and ESP Building shall be provided with motor operated fire dampers. These dampers shall close in case of fire on receiving signals from the Fire Detection and Protection System.