Meja Thermal Power Project ( 2 X 660 MW) – CW System Equipment package
Bidding Document No.:
Salient Technical Features:
“Salient Technical Features of the equipment/systems/services covered in IFB no 40025210 dated 08.08.2013 are mentioned below. These Salient Technical features are mentioned only to facilitate the prospective bidders to
Brief Scope:
The scope of work includes design, manufacture, engineering, inspection and testing at suppliers works, packing, forwarding to site, unloading, erection, supervision, pre- commissioning, testing and commissioning, and performance testing of equipment/system of the CW system equipment package and furnishing of spares as per specifications and scope defined in the bidding documents
Salient Features of major system & equipments are as follows:
A) CW system equipments
1) CW pumps with associated motors.
a)Type of CW
b) Total no of pumps |
:Five (5) numbers. |
|
c) |
Rated discharge |
: 36000 cum/hr |
d) |
Total head |
: 25 MWC |
e)Operating speed (max) : 333 rpm
2)Five (5) nos of 2600mm hydraulically actuated butterfly valves in CW pump discharge.
Page 1 of 2
3) Two (2) nos of 2600mm electrically actuated butterfly valve for CW duct interconnection and 1400mm electrically actuated butterfly valve for recirculation line
5)Five (5) nos rubber expansion joint for CW pumps
6)One (1) no 60 tons capacity (minimum) Gantry crane
7)Required numbers of Air release valves
8)Duct interconnection and recirculation piping
9)Carrying out transient analysis and sump model studies.
10)Station auxiliary cooling water pumps (SACW) consisting of three(3) nos vertical pumps
B)1) Intake water system consisting of three(3) numbers vertical, Intakewell pumps
2)Makeup water system consisting of three(3) numbers vertical, Makeup water pumps
3)Silt flush pumps along with motor, valves & fittings, hoist.
4)VFD system for Intake well pumps and LT power & control cables required between VFD panels & Intake well pump motors
5)Carrying out transient analysis for makeup water system
C)Raw water system consisting of three(3) numbers vertical, Raw water (PT) pumps
D)Required instrumentation
Page 2 of 2