LT Switchgears & LT Busducts Package for Darlipalli STPP Stage-I 2X800MW)
 
Switchgear and LT Busducts package for Darlipalli STPP Stage-I (2X800MW). 
and  LT  Busducts  as  detailed  in  the  bidding  document  No.CS-9549-206-2  for  LT 
B. Salient Technical Features
storage at site, complete installation, testing and commissioning of entire LT Switchgears 
the  site  and  inland  transit  insurance,  delivery  at  site,  receipt,  unloading,  handling  and 
 
 
 
 
The scope includes design, manufacture, shop testing, packing, inland transportation to 
A. Brief Scope of Work
 
All switchboards shall be of metal enclosed, indoor, floor-mounted, free-standing type of 
 
The reference ambient temperature is 50 C for all the equipment. 
each  comprising  of  busbar  compartment,  switchgear  /  feeder  compartment,  cable 
compartment  or  cable  alley  and  control  compartment.  Entire  busbar  system  shall  be 
bolted design. All switchboards shall be divided into distinct vertical sections (panels), 
second and the Dynamic withstand rating shall be 105kA (peak). 
The  short-time  fault  withstand  rating  of  the  switchgears  shall  be  50kA  (RMS)  for  one 
 
 
 
insulated with PVC sleeves. Cable terminations located in cable alley shall be designed 
The  Circuit  Breakers  /  Contactors  shall  be  of  air  break  type  &  should  conform  to  the 
 
“Service” and “Test” positions. 
 
to meet the Form IV b Type 7 (as per IEC 60439) for safety purpose. The termination for 
each module shall have its own integral glanding facility. 
 
requirements of IS / IEC 60947. MCCB shall be provided for 100A, 125A, 160A, 250A & 
The circuit breaker will  normally be controlled from remote control panels (employer’s 
 
controlled. 
400A supply feeders. The motor feeders for 110kW & above shall be Air Circuit Breaker 
All ACDBs, DCDBs & Solenoid Valve DBs shall be of Fixed Module type. All 415V Circuit 
breaker  modules  and  MCC  modules  shall  be  of  fully  draw  out  type  having  distinct 
on  IEC  61850  to  communicate  with  the  data  concentrator  through  LAN.  The  auxiliary 
contacts of the MCCB shall be fed to the digital inputs available in the numerical relays 
possible from the switchgear SCADA system.  All the protective relays associated with 
Control,  Metering  and  Status  monitoring.  All  the  numerical  relays  shall  have 
the  Circuit  breaker  modules  shall  be  of  Numerical  communicable  type  for  Protection, 
DDCMIS) through closing and shunt trip coils. The control of the breakers shall also be 
of Incomer / bus coupler / motor circuit breaker feeders, for integration into the numerical 
 
relay network. The vendor’s scope includes Numerical relays, Ethernet switches, Data 
cables and Laptops (for programming of Numerical relays) for the above purpose. 
communications on three ports, local front port communication to laptop and dual ports