SALIENT TECHNICAL FEATURES
PLANT OVERVIEW
NTPC Talcher-Kaniha (TSTPS) plant is located in Kaniha block under Talcher sub-division of Angul district in the state of ODISHA.
Nearest Town: Talcher, 26 KMs
Nearest Railway Station: Talcher, 29 KMs
Nearest Airport: Bhubaneswar 180 KMs
INSTALLED CAPACITY
STAGE - I - 2 Units each 500 MW - Total 1000 MW
STAGE- II - 4 Units each 500 MW - Total 2000 MW
Area of Work
Gasket Replacement for Generator Transformers (BHEL make 200MVA, 21/400KV) at Talcher -Kaniha Plant.
Brief Scope of Work
- The Work includes draining of generator transformer oil, replacement of gaskets/O-rings/Teflon washers etc. except bell tank gasket, transformer dry out, oil processing & refilling of oil as detailed in scope of work.
- The job also includes internal inspection of transformer, tap changer cleaning & gasket replacement works as mentioned in BOQ items of the contract proposal.
- The supplies of Gaskets/O-rings/Teflon washers etc are also included in the scope as detailed in the proposal.
- The work is to be carried out during Unit overhauling/ shutdown opportunities within stipulated timeframe on continuous basis as detailed in scope of work.
- The scope of work mentioned here is in brief, for detail may refer the detailed technical specification, Bill of quantity and Terms & condition.