The Salient Technical Features are as follows:
|
Sr. No. |
Equipment Name |
Rating |
Quantity |
|
1. |
Generator Transformers (GT) |
250MVA, 15.75/237 KV class, 3-phase with OCTC(+/-5%) |
2 Nos. |
|
2. |
Station Transformer |
16 MVA, 15.75/6.9 KV, with OLTC (+/-10%) |
2 Nos. |
|
3. |
Service Transformers |
2 MVA, 6.6/0.433 KV with OCTC(+/-5%) |
1 No. |
|
1.6 MVA, 6.6/0.433 KV with OCTC(+/-5%) |
1 No. |
||
|
1 MVA, 6.6/0.433 KV with OCTC(+/-5%) |
1 No. |
||
|
4. |
Online DGA Analyzer |
- |
2 Nos. |
|
5. |
Online Moisture Removal System |
- |
1 No. |
|
6. |
Spare Transformer Oil |
As specified |
5% (by Vol. |
|
7. |
Mandatory Spares |
As specified |
LOT |