NTPC Limited
(A Government of India Enterprise)
Badarpur Thermal Power Station
NOTICE INVITING TENDER (NIT)
FOR
Pressure / DP Transmitter - BTPS
(Domestic Competitive Bidding)
NIT No: 40048374 |
Date:02.01.2016 |
Bidding Document No: 100104421 |
|
1.0NTPC invites
2.0Brief Details
NIT No. |
40048374 |
NIT Date |
02.01.2016 |
Document Sale Commencement Date & Time |
02.01.2016 11:59:09 |
Document Sale Close Date & Time |
22.01.2016 16:00:00 |
Source of IFB/NIT |
Badarpur Thermal Power Station |
Contract Classification |
Equipment Supply |
Last Date and Time for Bid submission |
03.02.2016 15:00:00 |
Technical Opening Date & Time |
03.02.2016 15:15:00 |
Bid Opening Date & Time |
10.02.2016 15:00:00 |
Cost of Bidding Documents in INR |
1,182.00 |
EMD in INR |
32000.00 |
|
|
Last Query Date (if any) |
28.01.2016 |
3.0 Bid Security and Integrity Pact (if applicable) shall be submitted in a sealed envelope separately offline by the stipulated bid submission closing date and time at the address given below. Any bid without an acceptable Bid Security and Integrity Pact (if applicable) shall be treated as
4.0 A complete set of Bidding Documents may be downloaded by any interested Bidder on payment
5.0 Brief Scope of Work & other specific detail Pressure / DP Transmitter - BTPS
1. Smart type differential pressure transmitter Differential pressure:
Essential/Minimum Requirements.
1. Type of Transmitter :SMART Microprocessor based 2 wire types, HART protocol compatible. 2 Sensor Type: All types of sensor except LVDT
3 Accuracy: ± 0.1% of calibrated span ( minimum)
4. Output Signal range :
5.Turn down ratio: 30:1
6.Load impedance 500 ohm (min.)
7.Housing Weather proof as per
08.Over Pressure 150% of max. Operating pressure.
09.Connection (Electrical) Plug and socket type (Gold plated crimping connector from renowned supplier)
10.Process connection: Transmitter and manifold will be integrated & hence the manifold process connecting end must have ½ " BSP
(M) (with suitable connector to withstand pressure & temperature)that means the process connection available from indentor side is 1/2 inch BSP (F) & HENCE VENDOR WOULD SUPPLY ½ " BSP (M) END FOR FIXING OF MANIFOLD WITH PROCESS.
11.Span and Zero :Continuous, tamper proof, Remote as well as adjustability manual from instrument with zero suppression and elevation facility.
12.Accessories :
i)5 way / 3 way / 2 way (as per requirement of transmitter) manifold with valve for each DP/level/flow / gauge / pressure transmitters. Manifold body /bonnet material:
(Only from renowned manufacturers)
ii)Universal mounting steel bracket with steel bolts and washers suitable for wall / 2# size pipe mounting for each transmitter.
13.Diagnostics: Self Indicating feature
14.Power supply : 24V DC ± 10%.
15.Adjustment/calibration/maintenance With hand- held type universal calibrators compatible with HART protocol. Device Data to be updated to available HART communicator
16Damping: 0 to 10 seconds adjustable
17Square root capability: required
18 |
Ambient temperature |
: |
19 |
Output local indication |
: Minimum 4 ½ Digit Digital LCD display indicator configurable in engineering units, diagnostic error |
code / message. |
|
|
20 |
Process wetted parts : Sensor / diaphragm # SS or better suitable for application parameters as mentioned. |
2. Smart type differential pressure transmitter Differential pressure:
Essential/Minimum Requirements.
1. Type of Transmitter :SMART Microprocessor based 2 wire types, HART protocol compatible. 2 Sensor Type: All types of sensor except LVDT
3 Accuracy: ± 0.1% of calibrated span ( minimum)
4. Output Signal range :
5.Turn down ratio: 30:1
6.Load impedance 500 ohm (min.)
7.Housing Weather proof as per
08.Over Pressure 150% of max. Operating pressure.
09.Connection (Electrical) Plug and socket type (Gold plated crimping connector from renowned supplier)
10.Process connection: Transmitter and manifold will be integrated & hence the manifold process connecting end must have ½ " BSP
(M) (with suitable connector to withstand pressure & temperature)that means the process connection available from indentor side is 1/2 inch BSP (F) & HENCE VENDOR WOULD SUPPLY ½ " BSP (M) END FOR FIXING OF MANIFOLD WITH PROCESS.
11.Span and Zero :Continuous, tamper proof, Remote as well as adjustability manual from instrument with zero suppression and elevation facility.
12. Accessories :
i) 5 way / 3 way / 2 way (as per requirement of transmitter) manifold with valve for each DP/level/flow / gauge / pressure transmitters. Manifold body /bonnet material:
(Only from renowned manufacturers)
ii)Universal mounting steel bracket with steel bolts and washers suitable for wall / 2# size pipe mounting for each transmitter.
13.Diagnostics: Self Indicating feature
14.Power supply : 24V DC ± 10%.
15.Adjustment/calibration/maintenance With hand- held type universal calibrators compatible with HART protocol. Device Data to be updated to available HART communicator
16Damping: 0 to 10 seconds adjustable
17Square root capability: required
18 |
Ambient temperature |
: |
19 |
Output local indication |
: Minimum 4 ½ Digit Digital LCD display indicator configurable in engineering units, diagnostic error |
code / message. |
|
|
20 |
Process wetted parts : Sensor / diaphragm # SS or better suitable for application parameters as mentioned. |
3. DP TRANSMITTER, RANGE: 0 TO 1.6 KG/CM2, STATIC HEAD:400 KSC,Process Temp:200 deg C
Essential/Minimum Requirements.
1. Type of Transmitter :SMART Microprocessor based 2 wire types, HART protocol compatible. 2 Sensor Type: All types of sensor except LVDT
3 Accuracy: ± 0.1% of calibrated span ( minimum)
4. Output Signal range :
5.Turn down ratio: 30:1
6.Load impedance 500 ohm (min.)
7.Housing Weather proof as per
08.Over Pressure 150% of max. Operating pressure.
09.Connection (Electrical) Plug and socket type (Gold plated crimping connector from renowned supplier)
10.Process connection: Transmitter and manifold will be integrated & hence the manifold process connecting end must have ½ " BSP
(M) (with suitable connector to withstand pressure & temperature)that means the process connection available from indentor side is 1/2 inch BSP (F) & HENCE VENDOR WOULD SUPPLY ½ " BSP (M) END FOR FIXING OF MANIFOLD WITH PROCESS.
11.Span and Zero :Continuous, tamper proof, Remote as well as adjustability manual from instrument with zero suppression and elevation facility.
12.Accessories :
i) 5 way / 3 way / 2 way (as per requirement of transmitter) manifold with valve for each DP/level/flow / gauge / pressure transmitters. Manifold body /bonnet material:
(Only from renowned manufacturers)
iii)Universal mounting steel bracket with steel bolts and washers suitable for wall / 2# size pipe mounting for each transmitter.
13.Diagnostics: Self Indicating feature
14.Power supply : 24V DC ± 10%.
15.Adjustment/calibration/maintenance With hand- held type universal calibrators compatible with HART protocol. Device Data to be updated to available HART communicator
16Damping: 0 to 10 seconds adjustable
17Square root capability: required
18 |
Ambient temperature |
: |
19 |
Output local indication |
: Minimum 4 ½ Digit Digital LCD display indicator configurable in engineering units, diagnostic error |
code / message. |
|
|
20 |
Process wetted parts : Sensor / diaphragm # SS or better suitable for application parameters as mentioned. |
4. DP TRANSMITTER RANGE
Essential/Minimum Requirements.
1. Type of Transmitter :SMART Microprocessor based 2 wire types, HART protocol compatible. 2 Sensor Type: All types of sensor except LVDT
3 Accuracy: ± 0.1% of calibrated span ( minimum)
4. Output Signal range :
5.Turn down ratio: 30:1
6.Load impedance 500 ohm (min.)
7.Housing Weather proof as per
08.Over Pressure 150% of max. Operating pressure.
09.Connection (Electrical) Plug and socket type (Gold plated crimping connector from renowned supplier)
10.Process connection: Transmitter and manifold will be integrated & hence the manifold process connecting end must have ½ " BSP
(M) (with suitable connector to withstand pressure & temperature)that means the process connection available from indentor side is 1/2 inch BSP (F) & HENCE VENDOR WOULD SUPPLY ½ " BSP (M) END FOR FIXING OF MANIFOLD WITH PROCESS.
11.Span and Zero :Continuous, tamper proof, Remote as well as adjustability manual from instrument with zero suppression and elevation facility.
12.Accessories :
i) 5 way / 3 way / 2 way (as per requirement of transmitter) manifold with valve for each DP/level/flow / gauge / pressure transmitters. Manifold body /bonnet material:
(Only from renowned manufacturers)
ii)Universal mounting steel bracket with steel bolts and washers suitable for wall / 2# size pipe mounting for each transmitter.
13.Diagnostics: Self Indicating feature
14.Power supply : 24V DC ± 10%.
15.Adjustment/calibration/maintenance With hand- held type universal calibrators compatible with HART protocol. Device Data to be updated to available HART communicator
16Damping: 0 to 10 seconds adjustable
17Square root capability: required
18 |
Ambient temperature |
: |
19 |
Output local indication |
: Minimum 4 ½ Digit Digital LCD display indicator configurable in engineering units, diagnostic error |
code / message. |
|
|
20 |
Process wetted parts : Sensor / diaphragm # SS or better suitable for application parameters as mentioned. |
5. PR TRANSMITTER,
Essential/Minimum Requirements.
1. Type of Transmitter :SMART Microprocessor based 2 wire types, HART protocol compatible. 2 Sensor Type: All types of sensor except LVDT
3 Accuracy: ± 0.1% of calibrated span ( minimum)
4. Output Signal range :
5.Turn down ratio: 30:1
6.Load impedance 500 ohm (min.)
7.Housing Weather proof as per
08.Over Pressure 150% of max. Operating pressure.
09.Connection (Electrical) Plug and socket type (Gold plated crimping connector from renowned supplier)
10.Process connection: Transmitter and manifold will be integrated & hence the manifold process connecting end must have ½ " BSP
(M) (with suitable connector to withstand pressure & temperature)that means the process connection available from indentor side is 1/2 inch BSP (F) & HENCE VENDOR WOULD SUPPLY ½ " BSP (M) END FOR FIXING OF MANIFOLD WITH PROCESS.
11.Span and Zero :Continuous, tamper proof, Remote as well as adjustability manual from instrument with zero suppression and elevation facility.
12.Accessories :
i) 5 way / 3 way / 2 way (as per requirement of transmitter) manifold with valve for each DP/level/flow / gauge / pressure transmitters. Manifold body /bonnet material:
(Only from renowned manufacturers)
ii)Universal mounting steel bracket with steel bolts and washers suitable for wall / 2# size pipe mounting for each transmitter.
13.Diagnostics: Self Indicating feature
14.Power supply : 24V DC ± 10%.
15.Adjustment/calibration/maintenance With hand- held type universal calibrators compatible with HART protocol. Device Data to be updated to available HART communicator
16Damping: 0 to 10 seconds adjustable
17Square root capability: required
18 Ambient temperature :
19 Output local indication : Minimum 4 ½ Digit Digital LCD display indicator configurable in engineering units, diagnostic error code / message.
20 Process wetted parts : Sensor / diaphragm # SS or better suitable for application parameters as mentioned
6. PR TRANSMITTER,
Essential/Minimum Requirements.
1. Type of Transmitter :SMART Microprocessor based 2 wire types, HART protocol compatible. 2 Sensor Type: All types of sensor except LVDT
3 Accuracy: ± 0.1% of calibrated span ( minimum)
4. Output Signal range :
5.Turn down ratio: 30:1
6.Load impedance 500 ohm (min.)
7.Housing Weather proof as per
08.Over Pressure 150% of max. Operating pressure.
09.Connection (Electrical) Plug and socket type (Gold plated crimping connector from renowned supplier)
10.Process connection: Transmitter and manifold will be integrated & hence the manifold process connecting end must have ½ " BSP
(M) (with suitable connector to withstand pressure & temperature)that means the process connection available from indentor side is 1/2 inch BSP (F) & HENCE VENDOR WOULD SUPPLY ½ " BSP (M) END FOR FIXING OF MANIFOLD WITH PROCESS.
11.Span and Zero :Continuous, tamper proof, Remote as well as adjustability manual from instrument with zero suppression and elevation facility.
12.Accessories :
i) 5 way / 3 way / 2 way (as per requirement of transmitter) manifold with valve for each DP/level/flow / gauge / pressure transmitters. Manifold body /bonnet material:
(Only from renowned manufacturers)
ii)Universal mounting steel bracket with steel bolts and washers suitable for wall / 2# size pipe mounting for each transmitter.
13.Diagnostics: Self Indicating feature
14.Power supply : 24V DC ± 10%.
15.Adjustment/calibration/maintenance With hand- held type universal calibrators compatible with HART protocol. Device Data to be updated to available HART communicator
16Damping: 0 to 10 seconds adjustable
17Square root capability: required
18 |
Ambient temperature |
: |
19 |
Output local indication |
: Minimum 4 ½ Digit Digital LCD display indicator configurable in engineering units, diagnostic error |
code / message. |
|
|
20 |
Process wetted parts : Sensor / diaphragm # SS or better suitable for application parameters as mentioned |
7. SMART PRESSURE TRANSMITTER : RANGE : 0 - 4 KG/CM SQ. , Process Temp 200 deg C.
Essential/Minimum Requirements.
1. Type of Transmitter :SMART Microprocessor based 2 wire types, HART protocol compatible. 2 Sensor Type: All types of sensor except LVDT
3 Accuracy: ± 0.1% of calibrated span ( minimum)
4. Output Signal range :
5.Turn down ratio: 30:1
6.Load impedance 500 ohm (min.)
7.Housing Weather proof as per
08.Over Pressure 150% of max. Operating pressure.
09.Connection (Electrical) Plug and socket type (Gold plated crimping connector from renowned supplier)
10.Process connection: Transmitter and manifold will be integrated & hence the manifold process connecting end must have ½ " BSP
(M) (with suitable connector to withstand pressure & temperature)that means the process connection available from indentor side is 1/2 inch BSP (F) & HENCE VENDOR WOULD SUPPLY ½ " BSP (M) END FOR FIXING OF MANIFOLD WITH PROCESS.
11.Span and Zero :Continuous, tamper proof, Remote as well as adjustability manual from instrument with zero suppression and elevation facility.
12.Accessories :
i) 5 way / 3 way / 2 way (as per requirement of transmitter) manifold with valve for each DP/level/flow / gauge / pressure
transmitters. Manifold body /bonnet material:
ii)Universal mounting steel bracket with steel bolts and washers suitable for wall / 2# size pipe mounting for each transmitter.
13.Diagnostics: Self Indicating feature
14.Power supply : 24V DC ± 10%.
15.Adjustment/calibration/maintenance With hand- held type universal calibrators compatible with HART protocol. Device Data to be updated to available HART communicator
16Damping: 0 to 10 seconds adjustable
17Square root capability: required
18 |
Ambient temperature |
: |
19 |
Output local indication |
: Minimum 4 ½ Digit Digital LCD display indicator configurable in engineering units, diagnostic error |
code / message. |
|
|
20 |
Process wetted parts : Sensor / diaphragm # SS or better suitable for application parameters as mentioned |
8. SMART DP TX 0 TO 1000 MMWCL STPR:250 KSC, Process Temp 200 deg C.
Essential/Minimum Requirements.
1. Type of Transmitter :SMART Microprocessor based 2 wire types, HART protocol compatible. 2 Sensor Type: All types of sensor except LVDT
3 Accuracy: ± 0.1% of calibrated span ( minimum)
4. Output Signal range :
5.Turn down ratio: 30:1
6.Load impedance 500 ohm (min.)
7.Housing Weather proof as per
08.Over Pressure 150% of max. Operating pressure.
09.Connection (Electrical) Plug and socket type (Gold plated crimping connector from renowned supplier)
10.Process connection: Transmitter and manifold will be integrated & hence the manifold process connecting end must have ½ " BSP
(M) (with suitable connector to withstand pressure & temperature)that means the process connection available from indentor side is 1/2 inch BSP (F) & HENCE VENDOR WOULD SUPPLY ½ " BSP (M) END FOR FIXING OF MANIFOLD WITH PROCESS.
11.Span and Zero :Continuous, tamper proof, Remote as well as adjustability manual from instrument with zero suppression and elevation facility.
12.Accessories :
i) 5 way / 3 way / 2 way (as per requirement of transmitter) manifold with valve for each DP/level/flow / gauge / pressure transmitters. Manifold body /bonnet material:
(Only from renowned manufacturers)
ii)Universal mounting steel bracket with steel bolts and washers suitable for wall / 2# size pipe mounting for each transmitter.
13.Diagnostics: Self Indicating feature
14.Power supply : 24V DC ± 10%.
15.Adjustment/calibration/maintenance With hand- held type universal calibrators compatible with HART protocol. Device Data to be updated to available HART communicator
16Damping: 0 to 10 seconds adjustable
17Square root capability: required
18 |
Ambient temperature |
: |
19 |
Output local indication |
: Minimum 4 ½ Digit Digital LCD display indicator configurable in engineering units, diagnostic error |
code / message. |
|
|
20 |
Process wetted parts : Sensor / diaphragm # SS or better suitable for application parameters as mentioned |
9. DP TRANSMITTER
Essential/Minimum Requirements.
1. |
Type of Transmitter :SMART Microprocessor based 2 wire types, HART protocol compatible. |
|
2 |
Sensor Type: All types of sensor except LVDT |
|
3 |
Accuracy: ± 0.1% of calibrated span ( minimum) |
|
4. |
Output Signal range : |
|
5. |
Turn down ratio: 30:1 |
6.Load impedance 500 ohm (min.)
7.Housing Weather proof as per
08.Over Pressure 150% of max. Operating pressure.
09.Connection (Electrical) Plug and socket type (Gold plated crimping connector from renowned supplier)
10.Process connection: Transmitter and manifold will be integrated & hence the manifold process connecting end must have ½ " BSP
(M) (with suitable connector to withstand pressure & temperature)that means the process connection available from indentor side is 1/2 inch BSP (F) & HENCE VENDOR WOULD SUPPLY ½ " BSP (M) END FOR FIXING OF MANIFOLD WITH PROCESS.
11.Span and Zero :Continuous, tamper proof, Remote as well as adjustability manual from instrument with zero suppression and elevation facility.
12.Accessories :
i) 5 way / 3 way / 2 way (as per requirement of transmitter) manifold with valve for each DP/level/flow / gauge / pressure transmitters. Manifold body /bonnet material:
(Only from renowned manufacturers)
ii)Universal mounting steel bracket with steel bolts and washers suitable for wall / 2# size pipe mounting for each transmitter.
13.Diagnostics: Self Indicating feature
14.Power supply : 24V DC ± 10%.
15.Adjustment/calibration/maintenance With hand- held type universal calibrators compatible with HART protocol. Device Data to be updated to available HART communicator
16Damping: 0 to 10 seconds adjustable
17Square root capability: required
18 |
Ambient temperature |
: |
19 |
Output local indication |
: Minimum 4 ½ Digit Digital LCD display indicator configurable in engineering units, diagnostic error |
code / message. |
|
|
20 |
Process wetted parts : Sensor / diaphragm # SS or better suitable for application parameters as mentioned |
10. PR TRANSMITTER
Essential/Minimum Requirements.
1. Type of Transmitter :SMART Microprocessor based 2 wire types, HART protocol compatible. 2 Sensor Type: All types of sensor except LVDT
3 Accuracy: ± 0.1% of calibrated span ( minimum)
4. Output Signal range :
5.Turn down ratio: 30:1
6.Load impedance 500 ohm (min.)
7.Housing Weather proof as per
08.Over Pressure 150% of max. Operating pressure.
09.Connection (Electrical) Plug and socket type (Gold plated crimping connector from renowned supplier)
10.Process connection: Transmitter and manifold will be integrated & hence the manifold process connecting end must have ½ " BSP
(M) (with suitable connector to withstand pressure & temperature)that means the process connection available from indentor side is 1/2 inch BSP (F) & HENCE VENDOR WOULD SUPPLY ½ " BSP (M) END FOR FIXING OF MANIFOLD WITH PROCESS.
11.Span and Zero :Continuous, tamper proof, Remote as well as adjustability manual from instrument with zero suppression and elevation facility.
12.Accessories :
i) 5 way / 3 way / 2 way (as per requirement of transmitter) manifold with valve for each DP/level/flow / gauge / pressure transmitters. Manifold body /bonnet material:
(Only from renowned manufacturers)
ii)Universal mounting steel bracket with steel bolts and washers suitable for wall / 2# size pipe mounting for each transmitter.
13.Diagnostics: Self Indicating feature
14.Power supply : 24V DC ± 10%.
15.Adjustment/calibration/maintenance With hand- held type universal calibrators compatible with HART protocol. Device Data to be updated to available HART communicator
16Damping: 0 to 10 seconds adjustable
17Square root capability: required
18 |
Ambient temperature |
: |
19 |
Output local indication |
: Minimum 4 ½ Digit Digital LCD display indicator configurable in engineering units, diagnostic error |
code / message. |
|
|
20 |
Process wetted parts : Sensor / diaphragm # SS or better suitable for application parameters as mentioned |
11. DP TRANSMITTER,
Essential/Minimum Requirements.
1. Type of Transmitter :SMART Microprocessor based 2 wire types, HART protocol compatible. 2 Sensor Type: All types of sensor except LVDT
3 Accuracy: ± 0.1% of calibrated span ( minimum)
4. Output Signal range :
5.Turn down ratio: 30:1
6.Load impedance 500 ohm (min.)
7.Housing Weather proof as per
08.Over Pressure 150% of max. Operating pressure.
09.Connection (Electrical) Plug and socket type (Gold plated crimping connector from renowned supplier)
10.Process connection: Transmitter and manifold will be integrated & hence the manifold process connecting end must have ½ " BSP
(M) (with suitable connector to withstand pressure & temperature)that means the process connection available from indentor side is 1/2 inch BSP (F) & HENCE VENDOR WOULD SUPPLY ½ " BSP (M) END FOR FIXING OF MANIFOLD WITH PROCESS.
11.Span and Zero :Continuous, tamper proof, Remote as well as adjustability manual from instrument with zero suppression and elevation facility.
12.Accessories :
i) 5 way / 3 way / 2 way (as per requirement of transmitter) manifold with valve for each DP/level/flow / gauge / pressure transmitters. Manifold body /bonnet material:
(Only from renowned manufacturers)
ii)Universal mounting steel bracket with steel bolts and washers suitable for wall / 2# size pipe mounting for each transmitter.
13.Diagnostics: Self Indicating feature
14.Power supply : 24V DC ± 10%.
15.Adjustment/calibration/maintenance With hand- held type universal calibrators compatible with HART protocol. Device Data to be updated to available HART communicator
16Damping: 0 to 10 seconds adjustable
17Square root capability: required
18 |
Ambient temperature |
: |
19 |
Output local indication |
: Minimum 4 ½ Digit Digital LCD display indicator configurable in engineering units, diagnostic error |
code / message. |
|
|
20 |
Process wetted parts : Sensor / diaphragm # SS or better suitable for application parameters as mentioned |
6.0 Prospective bidders from U.P. State are compulsorily required to provide TIN number at the time of purchase of bidding documents.
7.0Qualifying Requirements for Bidders:
1.0The Bidder should be a manufacturer of Pressure/DP Transmitters.
1.1The bidder should have executed any one of the following Similar Works In India in the preceding seven years as on the date of opening of
One Work of value not less than Rs 12.75 lacs (Rupee Twelve lakh and Seventy five thousand only)
OR
Two works of value not less than Rs 7.97 lacs (Rupee Seven lakh and Ninety Seven thousand only) each.
OR
Three works of value not less than of Rs 6.37 lacs (Rupee Six lakh and Thirty Seven thousands only) each.
Note:
1.2 #Similar# works means any work which includes #supply of pressure / DP transmitter to power plant or any process industry #.
1.3The work #executed# mentioned above means the bidder should have achieved the criteria specified above, even if the total contract is started earlier and/ or is not completed/ closed.
1.4In case of orders under execution, the value of work executed till the date of opening of
1.5The average annual turnover of the bidder in the preceding three financial years as on the date of opening of
Note:
1.6While computing the annual turnover other income shall not be considered.
1.7In case where audited results for the last preceding financial year are not available certification of financial statements from a practicing Chartered Accountant shall be considered acceptable.
8.0Issuance of Bidding Documents to any bidder shall not construe that bidder is considered qualified.
9.0 NTPC reserves the right to reject any or all bids or cancel/withdraw the NIT for the subject package without assigning any reason whatsoever and in such case no bidder/intending bidder shall have any claim arising out of such action.
10.0 Address for Communication
S.K Srivastava Sr.Manager(Pur), 9650999606
Websites: https://etender.ntpclakshya.co.in/sap/bc/gui/sap/its/bbpstart or www.ntpctender.com or www.ntpc.co.in